Sdir' Setpoint Direction; Spra' Setpoint Split Range Start / '9.Spre' Setpoint Split Range End - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Parameterizing/addressing
9.4 Description of parameters
9.4.2.2

'7.SDIR' Setpoint direction

Possible settings:
Purpose:
Factory setting:
9.4.2.3

'8.SPRA' Setpoint split range start / '9.SPRE' Setpoint split range end

Adjustment range:
Purpose:
Factory setting:
160
• riSE
• FALL
This parameter is used to set the setpoint direction. The setpoint
direction is used to reverse the direction of action of the setpoint.
• Rising (riSE): A higher value at the setpoint input results in
opening of the valve.
• Falling (FALL): A higher value at the setpoint input results in
closing of the valve.
The setpoint direction is primarily used for split-range mode and
for single-acting actuators with the safety setting "uP".
riSE
0.0 ... 100.0
With these two parameters in combination with parameter
"'7.SDIR' Setpoint direction (Page 160)", you can limit the effective
setpoint. This allows split range tasks with the following character-
istic curves to be solved:
• rising/falling
• falling/rising
• falling/falling
• rising/rising
With "SPRA": 0.0
With "SPRE": 100.0
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12