ABB i-bus KNX Product Manual page 213

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Group objects
No.
48
This group object is always visible in controller mode.
This group object is hidden in actuator mode.
The group object receives the operating mode to be set as a 1-byte value.
Telegram value:
• 1: Comfort
• 2: Standby
• 3: Economy
• 4: Frost/heat protection
The operating mode switches between different operating states of the room:
Comfort: Room occupied. The setpoint temperature is set to a default value perceived as pleasant by most users.
Standby: Room is briefly/recently vacant. The setpoint temperature is decreased (heating) or increased (cooling)
Economy: The room is unused for an extended period (e.g. overnight), and the temperature is markedly decreased
(heating) or increased (cooling).
Frost/heat protection: The room or building is unused for an extended period (e.g. school during vacation). The setpoint
temperatures are adjusted to the minimum (heating – frost protection) or maximum (cooling – heat protection) values that
are still acceptable without damaging the installation.
Switchover between the operating modes usually takes place via a central schedule or via Intelligent Building Control.
The group objects and states Override mode, Fill level alarm, Dew point alarm, Window contact, Request On/Off (Master),
Presence detector and Operating mode (listed in decreasing priority) determine the controller's setpoint temperature
in addition to manual setpoint adjustment and basic setpoint adaptation.
If a slave is used:
To indicate the operating mode on a slave, this group object must be connected to the slave's group object Operating mode
(slave).
Object function
Operating mode normal (master)
Note
Note
Name
Channel A – Controller
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 211
Data type
Flags
1 byte
C, W, T, U
DPT 20.102