Insulation Tests - ABB REX640 Product Manual

Hide thumbs Also See for REX640:
Table of Contents

Advertisement

REX640
Product version: 1
Table 28. Electromagnetic compatibility tests, continued
Description
Power frequency immunity test
• Common mode
• Differential mode
Conducted common mode disturbances
Emission tests
• Conducted
0.15...0.50 MHz
0.5...30 MHz
• Radiated
30...230 MHz
230...1000 MHz
1...3 GHz
3...6 GHz
Table 29. Insulation tests
Description
Overvoltage category
Pollution degree
Insulation class
Dielectric tests
Impulse voltage test
Insulation resistance measurements
Protective bonding resistance
ABB
Type test value
Binary inputs only
300 V rms
150 V rms
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
<79 dB (µV) quasi peak
<66 dB (µV) average
<73 dB (µV) quasi peak
<60 dB (µV) average
<40 dB (µV/m) quasi peak, measured at 10 m
distance
<47 dB (µV/m) quasi peak, measured at 10 m
distance
<76 dB (µV/m) peak
<56 dB (µV/m) average, measured at 3 m
distance
<80 dB (µV/m) peak
<60 dB (µV/m) average, measured at 3 m
distance
Type test value
III
2
Class I
2 kV, 50 Hz, 1 min
1 kV, 50 Hz, 1 min, across open contacts
500 V, 50 Hz, 1 min, communication
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J, communication
>100 MΩ, 500 V DC
<0.1 Ω, 4 A, 60 s
1MRS759144 A
Reference
IEC 61000-4-16
IEC 60255-26, class A
IEC 61000-4-16
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
Reference
IEC 60255-27
IEC 60255-27
IEC 60255-27
IEC 60255-27
IEC 60255-27
IEC 60255-27
IEC 60255-27
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents