Siemens SINAMICS S120 Operating Instructions Manual page 30

Cabinet modules operator panel (option k08)
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
3.4 Initial commissioning
Note
Enter the motor-side filter
A filter on the motor side must be entered in p0230:
• Option L07 – dv/dt filter compact plus Voltage Peak Limiter: p0230 = 2
• Option L08 – motor reactor: p0230 = 1
• Option L10 – dv/dt filter plus Voltage Peak Limiter: p0230 = 2
When p0230 = 4 "External sine-wave filter", a separate sine-wave filter can be entered. An
input mask for specific filter data then appears.
NOTICE
Damage to the dv/dt filter if it is not activated during commissioning
The dv/dt filter may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter during commissioning.
Note
Motor reactor
If a motor reactor (option L08) is deployed, the option selection must be activated, otherwise
the closed-loop motor control will not be able to operate in an optimum fashion.
30
Cabinet Modules Operator Panel AOP30
Operating Instructions, 04/2014, A5E03263551A