Commissioning
3.4 Initial commissioning
3.4.2

First commissioning: infeed

General
Due to the modular design and the variety of applications for the SINAMICS S120 Cabinet
Modules drive system, a variety of Line Modules may be used. Depending on the infeed
used, some different parameters will have to be set during first commissioning. First
commissioning of the various Line Modules (Basic Line Modules, Smart Line Modules and
Active Line Modules) is described in the sections below.
The procedures described below are examples; they may vary depending on the plant
constellation.
Note
p0840 - setting the signal source for the "ON/OFF (OFF1)" command
Parameter p0840 must be supplied, e.g. through the following interconnections:
• set constant to 1
• from {VECTOR} p0863 bit 1 (close contactor)
• from the higher-level control
3.4.2.1

Basic Line Module

First commissioning: infeed
Table 3- 2
22
Data input with infeed via a Basic Line Module
• Input of the supply voltage in V.
• Input of the source of the ON/OFF1
command.
Navigate within the selection fields with
<F2> and <F3>.
Activate your selection with <F5>.
Once you have entered the final value,
choose "Continue" to exit the screen.
Cabinet Modules Operator Panel AOP30
Operating Instructions, 04/2014, A5E03263551A