7.1.2

Supported SNMP Features

The PROFINET Controller supports:
SNMPv1 and SNMPv2c
MIB-II (see RFC 1213 for details)
LLDP MIB (see IEEE 802.1AB for details)
LLDP 802.3 Extension MIB (see IEEE 802.1AB for details)
The PROFINET Controller does not:
Support SNMPv3.
Provide asynchronous notifications via SNMP.
Generate SNMP TRAP or INFORM messages.
7.1.3

SNMP Read Access

SNMP provides standard commands that allow a client to read SNMP data. The PROFINET Controller supports
these commands:
GET
GETNEXT
GETBULK
The SNMP Community strings supported for read access are:
public
18
pub
18
icmp
18
private
18
priv
18
ge_pnc
19
These community strings are fixed and cannot be changed.
7.1.4

SNMP Write Access

SNMP should not be used to change parameters on the PROFINET Controller module.
For PNC001 firmware version 2.05 and earlier, the SNMP SET command succeeds for the variables in some
MIBs/groups, but fails for the variables in other MIBs/groups. Changes made using SNMP SET change only
the SNMP variable itself, do not affect the PNC001 module operation, and are not saved across a power-
cycle or restart. For example, setting the sysName variable from the System Group does not change the
Device Name of the PNC001 module.
The SNMP Set command for PNC001 firmware version 2.10 and later is disabled.
18
Requires PNC firmware version 2.05 or later.
19
Requires PNC firmware version 2.10 or later.