Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
WARNING
troubleshooting of the Multi V product.
Table 73: Error Codes, continued.
Error Code
Communication error between master outdoor unit main
5
2
1
PCB and inverter PCB.
Communication error between slave1 outdoor unit main
5
2
2
PCB and inverter PCB.
Communication error between slave2 outdoor unit main
5
2
3
PCB and inverter PCB.
Communication error between master outdoor unit main
5
3
1
PCB and indoor unit(s) PCB.
Communication error between slave1 outdoor unit main
5
3
2
PCB and indoor unit(s) PCB.
Communication error between slave2 outdoor unit main
5
3
3
PCB and indoor unit(s) PCB.
Master outdoor unit main PCB and inverter PCB
5
7
1
communication error.
Slave1 outdoor unit main PCB and inverter PCB
5
7
2
communication error.
Slave2 outdoor unit main PCB and inverter PCB
5
7
3
communication error.
6
0
1 Master outdoor unit inverter PCB EEPROM error.
6
0
2 Slave1 outdoor unit inverter PCB EEPROM error.
6
0
3 Slave2 outdoor unit inverter PCB EEPROM error.
High temperature at the master outdoor unit inverter
6
2
1
heatsink.
High temperature at the slave1 outdoor unit inverter
6
2
2
heatsink.
High temperature at the slave2 outdoor unit inverter
6
2
3
heatsink.
Master outdoor unit inverter heatsink temperature
6
5
1
sensor error.
Slave1 outdoor unit inverter heatsink temperature
6
5
2
sensor error.
Slave2 outdoor unit inverter heatsink temperature
6
5
3
sensor error.
6
7
1 Master outdoor unit fan has locked up.
6
7
2 Slave1 outdoor unit fan has locked up.
6
7
3 Slave2 outdoor unit fan has locked up
7
1
1 Master outdoor unit inverter CT sensor error.
7
1
2 Slave1 outdoor unit inverter CT sensor error.
7
1
3 Slave2 outdoor unit inverter CT sensor error.
7
5
1 Master outdoor unit fan CT sensor error.
7
5
2 Slave1 outdoor unit fan CT sensor error.
7
5
3 Slave2 outdoor unit fan CT sensor error.
Description
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
ERROR CODE TABLES
Details
• Communication error between main PCB and inverter PCB.
• Check connections at both sockets.
• Inspect interconnecting cable for wear.
• Check if outdoor unit to indoor unit(s) communications cable
disconnected or shorted.
• Check A terminals are connected to indoor unit A(3) (5 on 3 x
3 cassette) terminals; B(4) (6 on 3 x 3 cassette) terminals.
Master outdoor unit inverter PCB is not receiving signal from
main PCB.
Slave1 outdoor unit inverter PCB is not receiving signal from
main PCB.
Slave2 outdoor unit inverter PCB is not receiving signal from
main PCB.
• Verify the EEPROM is present and in the socket correctly.
• Check if all pins are in and are not bent.
• Check if notch in the chip lines up with the arrow on the
socket.
System shut off because of high temperatures at the master
outdoor unit inverter heatsink.
System shut off because of high temperatures at the slave1
outdoor unit inverter heatsink.
System shut off because of high temperatures at the slave2
outdoor unit inverter heatsink.
• Check the connection on the outdoor unit PCB.
• Thermistor shorted or opened.
• Check for 12 V DC between 12 V and GND (red to black) for
5 V DC.
• Check the Signal to GND (white to black) and use correct chart
from Troubleshooting section to compare with actual system
temperature.
No airflow.
Master outdoor unit is restricted.
Slave1 outdoor unit is restricted.
Slave2 outdoor unit is restricted.
Master outdoor unit fan current detection (CT) sensor discon-
nected or shorted.
Slave1 outdoor unit fan current detection (CT) sensor discon-
nected or shorted.
Slave2 outdoor unit fan current detection (CT) sensor discon-
nected or shorted.