Parameter list
PNU
Description
U736
Transmit data for second CB (higher slot letter)
(2736)
Selection of connectors whose contents must be injected as transmit data to
*
a communications board (CB) with a higher slot ID letter.
0 = connector K0000
(Z111)
1 = connector K0001
etc.
This parameter not only defines the transmit data, but also their position in
the transmit telegram.
i001:
Word 1 in PZD section of telegram
i002:
Word 2 in PZD section of telegram
...
i016:
Word 16 in PZD section of telegram
Status word 1 (K0032) should be linked to word 1.
n738
Display of PKW job from supplementary boards
(2738)
st
i001:
1
word of PKW job from 1
...
th
(Z110)
i004
4
word of PKW job from 1
st
(Z111)
i005:
1
word of PKW job from location 2
...
th
i008
4
word of PKW job from 2
st
i009:
1
word of PKW job from TB
...
th
i012:
4
word of PKW job from TB
Details refer to "Function diagrams", Section 8 Sheets Z110 and Z111
n739
Display of PKW response to supplementary boards
(2739)
st
i001:
1
word of PKW job from 1
...
th
(Z110)
i004
4
word of PKW job from 1
st
(Z111)
i005:
1
word of PKW job from location 2
...
th
i008
4
word of PKW job from 2
st
i009:
1
word of PKW job from TB
...
th
i012:
4
word of PKW job from TB
Details refer to "Function diagrams", Section 8 Sheets Z110 and Z111
11.85 Configuring the SIMOLINK board
U740
SLB Node address
(2740)
Node address of the SIMOLINK board (SLB) on the bus. The node address
defines the telegrams to which the relevant board has write access. The
*
node address also defines whether a node is to perform the additional
function of dispatcher.
(Z121)
0 =
Not 0 =
Only one node in a SIMOLINK ring may perform the function of dispatcher.
Node address 0 may not be assigned to any node if a higher-level PLC is
performing the dispatcher function as the SIMOLINK master. When an SLB
is selected to operate as dispatcher, all nodes must be assigned
consecutive addresses, starting with address 0 for the dispatcher.
i001: For first SLB in unit
i002: Reserved
11-162
st
CB
st
CB
nd
CB
st
CB
st
CB
nd
CB
Dispatcher (generates telegram circulation)
Transceiver
nd
CB
nd
CB
[SW 1.5 and later]
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
All connector
Ind: 16
numbers
FS=0
1
Type: L2
Ind: 12
Type: L2
Ind: 12
Type: L2
0 to 200
Ind: 2
1
FS=0
Type: O2
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
See
Change
(Access /
Status)
P052 = 3
Online
P052 = 3
P052 = 3
P052 = 3
P051 =40
Offline
6RX1700-0AD76