LG ED05K000E00 Installation Manual page 24

Energy storage system
Hide thumbs Also See for ED05K000E00:
Table of Contents

Advertisement

24
Installation
D
E
2
Round
Terminal
(A)
1 mm
F
Wire-end Ferrules
PE
15 mm
PE
Insert an AC cable through the AC cable gland.
WARNING
Before connecting an AC cable, make sure
that the AC circuit breaker of the power grid is
turned off securely.
Insert the AC cable into the cap of cable gland
before inserting cable into the product.
Assemble wire-end ferrules and round terminal
on each wire.
1. Strip the grounding wire (PE) about 15 mm
and insert a round terminal into the wire.
Recommended round terminal : 4.0 mm or
4.5 mm of inner diameter with tin plated
terminal
2. Crimp the round terminal using crimping tool
(A).
3. Strip remaining wires about 15 mm and
insert a wire-end ferrule into the wire.
4. Crimp the ferrule ends using crimping tool
(A).
NOTE
Cables, round terminal and wire-end ferrules
are not supplied on this product package. The
system installer is responsible for selecting
proper components for the installation.
Connect the grounding wire (PE) to the
grounding connector. (Torque of 1.5 ± 0.3 N.m)
NOTE
y Connect the equipment grounding before
connecting the AC wires to the AC circuit
breaker.
y Screw for grounding connection is not
supplied on this product package. Prepare
a M4 size screw with spring washer for the
grounding connection.

Advertisement

Table of Contents
loading