Installing / mounting
3.3 Control Unit installation
Fitting and removing the CU to the PM230 FSD to FSF
Note
PM230 FSD to FSF door
The actual door of the PM230 (FSD to FSF) has been removed from the illustration to make
the sequence of fitting simpler. The door, in reality, should never be removed from the
PM230 enclosure.
To fit the CU to the PM230 FSD to FSF the following procedure should be performed:
1. Open the PM door, using the supplied key.
2. Fit the CU to the PM as previously described above.
3. All wiring of the CU and PM should be completed before proceeding further (refer to the
wiring/connection section of this manual).
4. If an Operator Panel is to be used, ensure that the D-type adaptor is fitted to the CU D-
type connector.
5. If an Operator Panel is to be fitted, ensure it is fitted before the door is closed.
6. Ensure that all seals are intact to maintain the IP55 rating.
7. Close and lock the PM door.
Fitting the D-type adapter retaining bracket
Figure 3-9
Adapter cable bracket FSD to FSF
A special bracket has been designed to ensure that the D-type adapter is fixed securely to
the enclosure door. The bracket is fitted as shown in the figure below. The bracket and
fixings are supplied with the product.
32
Hardware Installation Manual, 11/2014, A5E35319202B AA
PM230 Power Module IP55