Due to the change of weather conditions, humidity etc., pressure or flow or speed viewed on the display, can change
lightly on equal pressure on the sensor. To restore the correct value, you need to reset the offset. To do this, you may
press at the same time the buttons STOP/RESET and MON when the engine is not working yet, and the vents of
pressure sensor are both opened.
The reset has to be performed only when the size on the display (pressure, velocity or flow)
with open vent is different from zero, when the device is on since at least 15 minutes.
In the case in which the inverter it had to go in alarm, TO INV REG visualizes to display the same code of alarm visualized
on the display of the inverter. To reset the alarm is enough to press button STOP/RESET.
Depending on the kind of inverter used, the dip-switch with two levers on the back of the box, has to be configured as
follows:
02/10/2015

PRESSURE / VELOCITY / FLOW RESET

CAUTION!

RESET INVERTER ALARM

SELECTION OF SERIAL COMMUNICATION TTL/RS485

VF-S11
VF-FS1
1=ON
1=OFF
2=ON
2=OFF
VF-NC3
VF-S15
1=OFF
1=OFF
2=OFF
2=OFF
VF-AS1
VF-PS1
1=OFF
1=OFF
2=OFF
2=OFF
VF-MB1
1=OFF
2=OFF
11 / 17
Manual_MITOS_VT6_AIR_ver3p3_eng