Reading/Writing Parameters From/To Devices Supporting Iqss - Mitsubishi Electric IQSS-R-E Reference Manual

Iq sensor solution, melsec iq-r/iq-f/l/q series, got2000, melipc
Table of Contents

Advertisement

7.2
Reading/Writing Parameters from/to Devices
Supporting iQSS
Parameters can be read from and written to a slave module.
Window
Operating procedure
• The data backup/restoration function is useful to read/write the parameters of multiple devices supporting
iQSS in a batch. (Page 171 Backing up/Restoring Data of Devices Supporting iQSS)
• The useful function (linkage with dedicated tools) for devices supporting iQSS can also be used in the
"AnyWireASLINK Configuration" window. (Page 323 Linkage with dedicated tools (association with
properties))
1.
Select a device supporting iQSS in the "AnyWireASLINK
Configuration" window, then right-click and select [Online] 
[Parameter Processing of Slave Module] from the shortcut
menu.
The "Parameter Processing of Slave Module" screen appears.
• Reading parameters
1.
Select "Parameter read".
2.
Select the checkbox of the parameter to be read.
3.
Click the [Execute] button.
The selected parameter is read and the value is displayed in the
column of "Read Value".
• Writing parameters
1.
Select "Parameter write".
2.
Select the checkbox of the parameter to be written.
3.
Enter a value in the column of "Write Value".
4.
Click the [Execute] button.
The value entered in the column of "Write Value" is written to the
device supporting iQSS.