Parameter data records
B.2 Structure of the parameter data records DI mode
Operation of the module behind a PROFIBUS DP interface module
If the module is operated behind a PROFIBUS DP interface module, the parameter data
records 0 and 1 are not read back. You get the diagnostics data records 0 and 1 for the read
back parameter data records 0 and 1. You can find more information in the Interrupts section
of the PROFIBUS DP interface module device manual on the Internet
(http://support.automation.siemens.com/WW/view/en/78324181).
B.2

Structure of the parameter data records DI mode

Assignment of data record and channel
For the configuration with 1 x 32 channels, the parameters are located in data records 0 to
31 and are assigned as follows:
● Data record 0 for channel 0
● Data record 1 for channel 1
● ...
● Data record 30 for channel 30
● Data record 31 for channel 31
For the configuration as a 4 x 8-channel module, the module has 4 submodules with eight
channels each. The parameters for the channels are located in data records 0 to 7 and are
assigned as follows:
● Data records 0 to 7 for channels 0 to 7 (submodule 1)
● Data records 0 to 7 for channels 8 to 15 (submodule 2)
● Data records 0 to 7 for channels 16 to 23 (submodule 3)
● Data records 0 to 7 for channels 24 to 31 (submodule 4)
Address the respective submodule for data record transfer.
46
DI 32x24VDC HF digital input module (6ES7521-1BL00-0AB0)
Manual, 09/2016, A5E03485935-AF