I/O Number Allocation
3.1 Basics of I/O Allocation
3.1.1 How to Count the I/O Numbers
Counting and expression of the I/O numbers
Since I/O numbers are handled in units of 16 points, they are expressed as a combination of a
device type code and the lowest-digit of a decimal or hexadecimal number.
E.g. In the case of an external input, X0 to X9 and XA to XF are used.
<Decimal>
0, 1, 2, 3 ..... 9
3.1.2 Concept of I/O Number Allocation
Examples of I/O Number Allocation
I/O numbers are determined by the status of unit attachment and the occupied I/O points
allocated to respective units.
Starting word numbers of input/output units and intelligent units
By default, the starting word number for the unit attached next to the CPU unit is set at "10",
and the I/O numbers start with X100 or Y100.
The starting word number for each unit can be freely changed in the "FP7 Configuration"
menu of the tool software FPWIN GR7.
How to count I/O numbers for units that have both inputs and outputs
In the case of a unit that has both inputs and outputs (e.g. mixed input/output units, intelligent
units), input numbers and output numbers start with the same value.
E.g. If input numbers for a mixed input/output unit are X100 to X11F, the unit's output
numbers are set at Y100 to Y11F.
I/O numbers allocated to the CPU unit
A fixed area is allocated to the COM port and the ET-LAN port.