3. Parameters

3.1. Communication parameters

Set up the drive parameters as follows. It is necessary to reset the drive to update the parameter.
This option doesn't operate if these parameters are not correctly set.
Communi
Title
cation No.
cmod
0003
Command mode selection
Frequency setting mode
fmod
0004
selection 1
Number of motor pole for
f856
0856
communication
Communication
f899
0899
reset

3.2. Communication parameters for IPE003Z

Communi
Title
cation No.
c001
C001
Scanner input 1 address
c002
C002
c003
C003
c004
C004
c005
C005
c006
C006
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Function
function
Function
Scanner input 2 address
Scanner input 3 address
Scanner input 4 address
Scanner input 5 address
Scanner input 6 address
Description
0: Terminal board
1: Panel keypad (including remote keypad)
2: RS485 communication
3: CANopen communication
4: Communcation option
0: Setting dial 1 (save even if power is off)
1: Terminal board VIA
2: Terminal board VIB
3: Setting dial 2 (press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input
1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
0: -
1: Reset (after execution: 0)
Description
0: None
1: fa06 (Communication command 1)
2: fa23 (Communication command 2)
3: fa07 (Frequency command, 0.01Hz)
5: fa50 (Terminal output data from comm.)
6: fa51 (Analog output (FM) data from comm.)
8: f601 (Stall prevention level, %)
13: acc (Acceleration time 1, 0.1s)*
14: dec (Deceleration time 1, 0.1s) *
15: ul (Upper limit, 0.01Hz)
16: vb (Torque boost value 1, 0.1%)
17: vlv (Base frequency voltage 1, 0.1V)
100: CMD
101: LFRD
0-101 (Same as c001)
0-101 (Same as c001)
0-101 (Same as c001)
0-101 (Same as c001)
0-101 (Same as c001)
- 9 -
E6581818
Setting
4
7
-
-
Default
2
3
100*
*
1
1
2
3
101*
*
-
-
-
-