manufacturer's details for the permitted battery charge current must be observed.
Further, the following, device-dependent values apply:
– SITOP UPS1600 10 A: Maximum permissible charge current 3,000 mA
Derating for T
– SITOP UPS1600 20 A: Maximum permissible charge current 4,000 mA
Derating for T
– SITOP UPS1600 40 A: Maximum permissible charge current 5,000 mA
Derating for T
Faulty battery voltage
If the battery voltage falls below this value, it is considered as being faulty by the
SITOP UPS1600 and is not charged.
3.7.8.8

Load / Save

Configurations made in the web server can be saved as zip file. Saved configurations can be
loaded back to the web server.
Procedure for saving the configuration
1. Select the "Hardware configuration" menu.
2. Select submenu "Load/Save".
3. The zip file now displayed can be saved as a file using the "Save target as" function of
the shortcut menu (call by pressing the right-hand mouse key).
4. Enter a file name.
5. Click on "OK" to save the configuration as zip file.
Procedure for loading the configuration
1. Select the "Hardware configuration" menu.
2. Select submenu "Load/Save".
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
> 40 °C or U
< 24 V: 2,000 mA
u
in
> 40 °C or U
< 24 V: 3,000 mA
u
in
> 40 °C or U
< 24 V: 3,000 mA
u
in
Engineering and remote access
3.7 Web server
157