ABB 2CSYK1102C/S Product Manual page 16

Switch actuator with rocker switches
Table of Contents

Advertisement

MYLOS
Building Automation
®
Options:
Minutes
- 0
- ...
- 5
- ...
- 1.000
Seconds
- 0
- ...
- 59
If the pre-warning time is different from "0", the stairlight time is extended with the pre-warning time.
"Stairlight time increases by means of multiple ON" parameter
If during stairlight time a further ON telegram is received, the remaining stairlight time can be extended with an
additional time.
This is possible until the maximum time has been reached. The maximum time can be programmed and set as 1,
2, 3, 4 or 5 times the stairlight time. If a part of the "increased" time has elapsed, it is taken back to the maximum
value. However it is not possible to exceed the maximum parametrised time. The pre-warning time is not modified
by the "increasing" action.
Options:
- no
- max. up to 1x stairlight time
- max. up to 2x stairlight time
- max. up to 3x stairlight time
- max. up to 4x stairlight time
- max. up to 5x stairlight time
With the "no" setting, a switching telegram ON is simply ignored.
The stairlight time passes without modifications until it is over.
If a simple boot function is required, "max. until 1x stairlight time" must be set. In this case the stairlight time is reset
by a new switching ON command on the telegram and it restarts from the beginning.
"Switchable stairlights" parameter
Here you can set the value of the telegram to be used for switching stairlight on and off in advance.
Options:
- ON with "1" and OFF with "0"
- ON with "1" no action with "0"
- ON with "0" or "1", switching off not possible
With the option "ON with '0' or '1', switching off not possible" the stairlight function is activated independently from
the incoming telegram value. In this case the advance switching off is not possible.
16 Commissioning | MYLOS