CHAPTER 5: SETTINGS
Table 5-41: Test mode operation
TEST MODE
In-service
FUNCTION
LED
Disabled
Unaffected
Isolated
Off
Forcible
Off
On restart, the
TEST MODE FORCING
their default states.
5.11.3 Phasor measurement unit test values
SETTINGS TESTING PMU TEST VALUES PMU 1(2) TEST VALUES
PMU 1
TEST VALUES
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
Test mode
Critical fail
TEST MODE
LED
relay
FORCING
Off
Normal
No effect
On
De-energized No effect
Flashing
De-energized Off
On
setting and the force contact input and force contact output settings revert to
PMU 1 TEST
FUNCTION: Disabled
PMU 1 VA TEST
MAGNITUDE: 500.00 kV
PMU 1 VA TEST
ANGLE: 0.00°
PMU 1 VB TEST
MAGNITUDE: 500.00 kV
PMU 1 VB TEST
ANGLE: –120.00°
PMU 1 VC TEST
MAGNITUDE: 500.00 kV
PMU 1 VC TEST
ANGLE: 120.00°
PMU 1 VX TEST
MAGNITUDE: 500.00 kV
PMU 1 VX TEST
ANGLE: 0.00°
PMU 1 IA TEST
MAGNITUDE: 1.000 kA
PMU 1 IA TEST
ANGLE: –10.00°
PMU 1 IB TEST
MAGNITUDE: 1.000 kA
PMU 1 IB TEST
ANGLE: –130.00°
PMU 1 IC TEST
MAGNITUDE: 1.000 kA
PMU 1 IC TEST
ANGLE: 110.00°
PMU 1 IG TEST
MAGNITUDE: 0.000 kA
Contact input and output behavior
Normal
Contact outputs disabled
Normal
Controlled by forcing features
Range: Enabled, Disabled
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
TESTING
5
5-327