Abb Standard Macro; Default I/O Connections; Select - ABB ACS150 User Manual

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

ABB Standard macro

This is the default macro. It provides a general purpose I/O configuration with three
constant speeds. Parameter values are the default values given in chapter
signals and
If you use other than the default connections presented below, see section
terminals

Default I/O connections

1...10 kohm
Alternative connection
for AI1. If used, switch
IU selector to U
(0...10 V voltage
signal).
1)
See parameter group
DI3 DI4 Operation (parameter)
0
1
0
1
parameters, starting from page 65.
on page 34.
I/O connection
SCR
AI
GND
3)
+10V
+24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
Relay connection
COM
NC
NO
12 CONSTANT
0 Set speed through
integrated potentiometer
0 Speed 1 (1202)
1 Speed 2 (1203)
1 Speed 3 (1204)
4)
Signal cable shield (screen)
Frequency reference: 0...20 mA
Analog input circuit common
Reference voltage: +10 VDC, max. 10 mA
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Constant speed selection
Constant speed selection
Acceleration and deceleration selection
5)
Relay output
No fault [Fault (-1)]
2)
SPEEDS:
0 = ramp times according to parameters
and 2203.
1 = ramp times according to parameters
and 2206.
3)
360 degree grounding under a clamp.
4)
Tightening torque = 0.22 N·m / 2 lbf. in.
5)
Tightening torque = 0.5 N·m / 4.4 lbf. in.
1)
1)
2)
Application macros
59
Actual
I/O
2202
2205

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs350

Table of Contents