Configuration In Step 7 - Siemens CP 1243-7 LTE Operating Instructions Manual

Simatic net
Table of Contents

Advertisement

Configuration

4.2 Configuration in STEP 7

4.2
Configuration in STEP 7
Configuration in STEP 7
You configure the modules, networks and connections in an engineering station in SIMATIC
STEP 7. You will find the required version in the section Requirements for operation
(Page 20).
You can configure a maximum of three CMs/CPs per station. If you insert several CPs in an
S7-1200, you can, for example, establish redundant communications paths.
Configuring communication with the CPU (data point configuration)
CP communication is not programmed using program blocks but configured using data
points.
One requirement for data point configuration is the programming of the assigned CPU and
the input and output data of the station. To assign the user data to be transferred
(input/output data) to the data points, you need to create PLC tags.
Overview of the configuration steps in STEP 7
Notes:
● No Ethernet network needs to be created for the communication via the mobile wireless
network.
● A telecontrol server or a TeleService- gateway cannot be configured in STEP 7.
Follow the steps below when configuring:
1. Create a STEP 7 project.
2. Insert the required SIMATIC stations.
3. Program the CPUs and the relevant inputs and outputs.
4. Create PLC tags for the input and output data to be transferred in the CPUs.
5. Insert the CPs in the relevant stations.
6. Configure the CPs including the data points and any messages (e-mail / SMS).
Note
Changing the project number or station number for the entire STEP 7 project
If you change the project number or the station number in the "CP identification"
parameter group for a telecontrol CP, these parameters are changed for all CPs in the
STEP 7 project.
7. If required, program the program blocks for S7 communication and Open User
Communication.
44
Operating Instructions, 04/2017, C79000-G8976-C381-03
CP 1243-7 LTE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-1200 telecontrolCp 1243-7 lte-euCp 1243-7 lte-us

Table of Contents