Haier MVAH018MV2AA Service Manual page 32

Constant air volume duct
Hide thumbs Also See for MVAH018MV2AA:
Table of Contents

Advertisement

Indoor power supply wiring & signal wiring between indoor and outdoor & signal wiring between indoor.
Items
Total
Current of
AWG(mm
Indoor Unite(A)
<7
≥7 and <11
≥11 and <16
≥16 and <22
≥22 and <27
•  The electrical power line and signal lines must be tightly.
•  Every indoor unit must have the ground connection.
•  The power line should be enlarged if it exceeds the permissible length.
•  Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side of signal 
lines of outdoor units grounded at one point.
•  Signal lines should not exceed 3280ft(1000m)
Signal Wiring of Wired controller
Length of Signal Line ft (m)
<328(100)
≥328(100)and <656(200)
≥656(100) and <984(300)
≥984(300) and <1312(400)
≥1312(400)and <1968(600)
The shielding lay of the signal line must be grounded at one end.
The total length of the signal line shall not be more than 600m.
Rated 
Cross
Length
Current of 
Section
in.(m)
Overflow 
2
)
Breaker(A)
14(2.5)
65.6(20)
12(4)
65.6(20)
10(6)
82(25)
8(8)
98.4(30)
6(10)
131(40)
Rated current of residual 
Circuit Breaker(A) 
Ground Fault 
Interruptor(mA)
Response time(S)
10
10 A, 30mA, 0.1S or below
16
16 A, 30mA, 0.1S or below
20
20 A, 30mA, 0.1S or below
32
32 A, 30mA, 0.1S or below
32
32 A, 30mA, 0.1S or below
Wiring Dimensions AWG (mm
22(0.3)×core shielding line
20(0.5)×core shielding line
18(0.754)×core shielding line
16(1.25)×core shielding line
14(2)×core shielding line