Haier MVAH018MV2AA Service Manual page 28

Constant air volume duct
Hide thumbs Also See for MVAH018MV2AA:
Table of Contents

Advertisement

9.Install outlet flange
Install outlet flange according to the needs, the outlet flange is standard component, bolts are laid in accessories 
box.
Note: You can select not to connect with the flange. Instead of it, you can use the round plastic air outlet (purchased 
by user)
10. Examples for Bad Installation
•  The unit is not equipped with the air return pipe and the inner side of the suspending ceiling is used as the blast 
pipe, causing the humidity increasing due to irregular air mass, strong wind or sunlight from the outside world.
•  There might be condensate dropping down at the outer side of the blast pipe. The humidity is high, even if the 
inner side of the suspended ceiling isn't used as a blast pipe in new concrete buildings. At this time, the whole 
body should use the thermo wool for heat preservation (the thermo wool can be packed with a steel wire).
•  It is operated under the conditions beyond the limits, leading to the overload of the compressor.
•  Affected by the capacity of the exhaust fan, and the strong wind and wind direction in the outer flue, when the 
blowing quantity of the air conditioner exceeds the limits, the drained water of the heat exchanger will overflow, 
causing water leakage.
11. Static Pressure GradeSetting
For MVAH036~048MV2AA units, after installation need to 
preliminary estimates external static pressure, according to the 
external static pressuresetting the unit's static pressure grade by 
controller.
Note: the detail operation methods for setting the unit's static 
pressure grade refer to the controller manual.
12. Refrigerant Tube
Tubing Permissible Length & Height Difference
Please refer to the attached manual of outdoor units.
Piping Materials & Heat Insulating Materials
As  to  prevent  condensation,  heat  insulating  treatment  should  be 
performed. The  heat  insulating  treatment  for  gas  and  liquid  piping 
should be done respectively.
Exhaust fan
Example of bad installation
The static pressure range of each gradeas 
follows:
26
ceiling
Grade
Static pressure range
1
0~25pa
2
25~75pa
3
75~125pa
4
125~175pa
5
175~200pa
Piping
Hard PVC tube
Material
VP1in(inner bore)
Heat Insulating
Vesicant polythene
Material
thickness: over 1/4in