GE C30 Instruction Manual page 334

Controller system ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 23 of 46)
ADDR
REGISTER NAME
FlexElement (Read/Write Setting) (16 modules)
9000
FlexElement™ 1 Function
9001
FlexElement™ 1 Name
9004
FlexElement™ 1 InputP
9005
FlexElement™ 1 InputM
B
9006
FlexElement™ 1 Compare
9007
FlexElement™ 1 Input
9008
FlexElement™ 1 Direction
9009
FlexElement™ 1 Hysteresis
900A
FlexElement™ 1 Pickup
900C
FlexElement™ 1 DeltaT Units
900D
FlexElement™ 1 DeltaT
900F
FlexElement™ 1 Pickup Delay
9010
FlexElement™ 1 Reset Delay
9011
FlexElement™ 1 Block
9012
FlexElement™ 1 Target
9013
FlexElement™ 1 Events
9014
...Repeated for FlexElement™ 2
9028
...Repeated for FlexElement™ 3
903C
...Repeated for FlexElement™ 4
9050
...Repeated for FlexElement™ 5
9064
...Repeated for FlexElement™ 6
9078
...Repeated for FlexElement™ 7
908C
...Repeated for FlexElement™ 8
90A0
...Repeated for FlexElement™ 9
90B4
...Repeated for FlexElement™ 10
90C8
...Repeated for FlexElement™ 11
90DC
...Repeated for FlexElement™ 12
90F0
...Repeated for FlexElement™ 13
9104
...Repeated for FlexElement™ 14
9118
...Repeated for FlexElement™ 15
912C
...Repeated for FlexElement™ 16
DCmA Outputs (Read/Write Setting) (24 modules)
9300
DCmA Output 1 Source
9301
DCmA Output 1 Range
9302
DCmA Output 1 Minimum
9304
DCmA Output 1 Maximum
9306
...Repeated for DCmA Output 2
930C
...Repeated for DCmA Output 3
9312
...Repeated for DCmA Output 4
9318
...Repeated for DCmA Output 5
931E
...Repeated for DCmA Output 6
9324
...Repeated for DCmA Output 7
932A
...Repeated for DCmA Output 8
9330
...Repeated for DCmA Output 9
9336
...Repeated for DCmA Output 10
933C
...Repeated for DCmA Output 11
9342
...Repeated for DCmA Output 12
9348
...Repeated for DCmA Output 13
934E
...Repeated for DCmA Output 14
9354
...Repeated for DCmA Output 15
935A
...Repeated for DCmA Output 16
9360
...Repeated for DCmA Output 17
9366
...Repeated for DCmA Output 18
B-30
RANGE
UNITS
0 to 1
---
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 1
0.1 to 50
-90 to 90
0 to 2
20 to 86400
0 to 65.535
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 2
–90 to 90
–90 to 90
C30 Controller System
APPENDIX B
STEP
FORMAT
---
1
F102
---
---
F206
---
1
F600
---
1
F600
---
1
F516
---
1
F515
---
1
F517
%
0.1
F001
pu
0.001
F004
---
1
F518
0 (Milliseconds)
---
1
F003
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
0 (Self-reset)
---
1
F102
---
1
F600
---
1
F522
0 (–1 to 1 mA)
pu
0.001
F004
pu
0.001
F004
DEFAULT
0 (Disabled)
"FxE 1"
0
0
0 (LEVEL)
0 (SIGNED)
0 (OVER)
30
1000
20
0
0
0
0 (Disabled)
0
0
1000
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents