[le_slots and communication terminals, 1, --_--]
Figure 4-3
(1)
Time synchronization G
(2)
Plug-in module position E
(3)
Plug-in module position F
(4)
Integrated Ethernet interface J
(5)
Protective grounding terminal
The following communication modules can be used for SIPROTEC 5:
Serial modules
Application: Communication to the substation automation technology via substation-control protocols
Protection interface (only optical serial modules) for interfacing to external communication converters for
short direct connections.
2 different communication protocols or 2 different applications can be operated on serial modules with 2
connections. The IEC 60870-5-103 protocol for the substation automation technology as well as a protec-
tion interface, for example, can be operated on a serial optical module for close range with 2 connec-
tions.
Assign the protocol application to the corresponding channel of the communication module with DIGSI 5.
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017
Plug-In Module Positions and Communication Terminals on the 1/3 Module, for Non-Modular
Devices (7xx82)
Plug-In Modules
4.2 Communication Modules