FLEXLOGIC
Operand type
USER-
PROGRAMMABLE
PUSHBUTTONS
Some operands can be re-named. These are the names of the breakers in the breaker control feature, the ID (identification)
of contact inputs and outputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or
ID of any of these operands, the assigned name appears in the relay list of operands. The default names are shown in the
FlexLogic operands table.
The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are
listed in the FlexLogic operators table.
Table 5-21: FlexLogic gate characteristics
Gates
NOT
OR
AND
NOR
NAND
XOR
5
5-176
Operand syntax
PUSHBUTTON 1 ON
PUSHBUTTON 1 OFF
ANY PB ON
PUSHBUTTON 2 to 6, 12, or 16
depending on front panel
Number of inputs
Output is '1' (= ON) if...
1
input is '0'
2 to 16
any input is '1'
2 to 16
all inputs are '1'
2 to 16
all inputs are '0'
2 to 16
any input is '0'
2
only one input is '1'
Operand description
Pushbutton number 1 is in the "On" position
Pushbutton number 1 is in the "Off" position
Any of 12 pushbuttons is in the "On" position
Same set of operands as PUSHBUTTON 1
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS