Ambient temperature in °C
Figure 5-6 Power loss dissipated
&XUYH



5HVXOW
From the diagram we can see that the following ambient temperatures are
obtained for a total power loss of 650 W:
Table 5-6
Closed with natural convection and forced ventilation
(Curve 3)
Open with through-ventilation (Curve 2)
Closed with heat exchanger (Curve 1)
If you install the S7-300 horizontally, you can use the following types of cabinet:
• open, with closed ventilation
• closed, with heat exchanger
VHH DOVR

Selection and installation of cabinets

S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
60
50
40
30
3
20
200
400
600
Closed cabinet with heat exchanger (heat exchanger size 11/6 (920 mm x 460
mm x 111 mm)
Cabinet with through-ventilation by natural convection
Closed cabinet with natural convection and forced ventilation by equipment
fans
Choice of cabinets
&DELQHW GHVLJQ
1
1 2
800
1000
1200
Loss of heat in W
&DELQHW 7\SH
0D[LPXP SHUPLWWHG DPELHQW
WHPSHUDWXUH
Operation not possible
approx. 38 °C
approx. 45 °C
&RQILJXULQJ
1400
5-15