The figure below shows the arrangement of eight signal modules in an S7-300
assembly.
Figure 5-4 Rack with eight signal modules
VHH DOVR

Arranging Modules on Multiple Racks


$UUDQJLQJ 0RGXOHV RQ 0XOWLSOH 5DFNV
([FHSWLRQV
With CPU 312 and CPU 312C, only a single-row configuration on a rack is
possible.
8VLQJ LQWHUIDFH PRGXOHV
If you are planning a structure distributed between multiple racks then you will
need interface modules (IM). Interface modules route the backplane bus of an
S7-300 to the next rack.
The CPU is always located on rack 0.
Table 5-4
Interface modules - Overview
&KDUDFWHULVWLFV
Send IM in rack 0
Receive IM in rack 1 to 3
Maximum number of
expansion modules
Length of the connecting
cables
Remarks
5-8
SF
SIEMENS
BUSF
DC5V
FRCE
RUN
STOP
PS
CPU
7ZR RU PRUH URZV
IM 360
Order No.: 6ES7 360-3AA01-0AA0
IM 361
Order No.: 6ES7 361-3CA01-0AA0
3
1 m (6ES7 368-3BB01-0AA0)
2.5 m (6ES7 368-3BC51-0AA0)
5 m (6ES7 368-3BF01-0AA0)
10 m (6ES7 368-3CB01-0AA0)
-
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
SM2 SM3
SM1
SM4
SM5 SM6
/RZFRVW URZ FRQILJXUDWLRQ
IM 365
Order No.: 6ES7 365-0AB00-0AA0
IM 365 (hardwired to send IM 365)
1
1 m (hardwired)
Rack 1 can only receive signal
modules; total current load is limited
to 1.2 A, whereby the maximum for
rack 1 is 0.8 A
These restrictions do not apply to
operation with interface modules
IM 360/IM 361
SM7
SM8
A5E00105492-03