Chapter 6
Certification
Section 6.3
Industry Canada Compliance
CAN ICES-3 (A) / NMB-3 (A)
Section 6.4
EMI and Environmental Type Tests
The RX5000 has passed the following EMI and environmental tests.
IEC 61850-3 EMI Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
36
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips & Interrupts
Voltage Dips & Interrupts
Damped Oscillatory
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
D.C Power ports
AC Power ports
Earth ground ports
Enclosure Ports
DC Power ports
AC Power ports
30% for 1 period, 60% for 50 periods
AC Power ports
Signal ports
Installation Guide
Test Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
+/- 2 kV line-to-earth,
+/- 1 kV line-to-line
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
10 V
10V
10V
10V
40 A/m, continuous,
1000 A/m for 1 s
1000 A/m for 1 s
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
100% for 5 periods,
100% for 50 periods
2.5 kV common, 1 kV
differential mode @1 MHz
Industry Canada Compliance
RUGGEDCOM RX5000
Severity
Levels
4
4
a
Note
a
Note
4
4
4
4
3
4
3
3
3
3
a
Note
5
3