108

Cable types

Cable sizing is based on NEC Table 310-16 for copper wires, 75°C (167°F) wire insulation at 40°C
(104°F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
earth (directly buried). For other conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
Copper cables with concentric copper shield
Max. load
current

Cable Entries

Input, DC link and motor cable (per phase) terminal sizes, accepted cable diameters
and tightening torques are given below
Frame size
Wire size
R5
R6
3/0 ... 350 MCM *
* with cable lugs 6...2/0 AWG, tightening torque 14.8...29.5 lbf ft

Dimensions, weights and noise

Frame size
R5
R6
Technical data
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Cable type
A
AWG/kcmil
31
10
44
8
57
6
75
4
88
3
101
2
114
1
132
1/0
154
2/0
176
3/0
202
4/0
224
250 MCM or 2 x 1
251
300 MCM or 2 x 1/0
273
350 MCM or 2 x 2/0
PDM code: 00096931-C
U1, V1, W1, U2, V2, W2, UDC+, UDC-
Wire Ø
(UL type 1)
AWG
in.
10...2/0
1.39
2.09
Height
Width
in.
in.
32.03
10.43
38.19
11.81
.
Tightening
torque
lbf ft
11.1
14.8...29.5
UL type 1
Depth
in.
15.35
17.28
Grounding PE
Wire size
Tightening
torque
AWG
lbf ft
10...2/0
11.1
5...4/0
5.9
Noise
Weight
lb
dB
143
70
220
73