Code Description
9906 MOTOR NOM CURR
Defines the nominal motor current.
• Must equal the value on the motor rating plate.
• Range allowed: 0.2...2.0 · I
9907 MOTOR NOM FREQ
Defines the nominal motor frequency.
• Range: 10...500 Hz (typically 50 or 60 Hz)
• Sets the frequency at which output voltage equals the
• Field weakening point = Nom Freq · Supply Volt / Mot Nom Volt
9908 MOTOR NOM SPEED
Defines the nominal motor speed.
• Must equal the value on the motor rating plate.
9909 MOTOR NOM POWER
Defines the nominal motor power.
• Must equal the value on the motor rating plate.
9910 ID RUN
This parameter controls a self-calibration process called the Motor ID Run. During this process, the drive operates
the motor (motor rotating) and makes measurements in order to identify motor characteristics and create a model
used for internal calculations. An ID Run is especially effective when:
• vector control mode is used [parameter
• operation point is near zero speed, and/or
• operation requires a torque range above the motor nominal torque, over a wide speed range, and without any
measured speed feedback (i.e. without a pulse encoder).
0 =
/
– The Motor ID Run process is not run. Identification magnetization is performed, depending on
OFF
IDMAGN
parameter 9904 and 2101 settings. In identification magnetization, the motor model is calculated at first start by
magnetizing the motor for 10 to 15 s at zero speed (motor not rotating). The model is recalculated always at start
after motor parameter changes.
• Parameter
9904
• Parameter
9904
magnetization is performed.
• Parameter
9904
): Identification magnetization is not performed.
BOOST
1 =
– Enables the Motor ID Run, during which the motor is rotating, at the next start command. After run
ON
completion, this value automatically changes to 0.
Note: The motor must be de-coupled from the driven equipment.
Note: If motor parameters are changed after ID Run, repeat the ID Run.
WARNING! The motor will run at up to approximately 50...80% of the nominal speed during the ID Run. The
motor will rotate in the forward direction.
Ensure that it is safe to run the motor before performing the ID Run!
See also section
How to perform the ID Run
(where I
is drive current).
2hd
2hd
9904
= 1 (
= 1 (
:
) or 2 (
VECTOR
SPEED
VECTOR
= 3 (
:
) and parameter
SCALAR
FREQ
= 3 (
:
) and parameter
SCALAR
FREQ
on page 39.
.
MOTOR NOM VOLT
:
) or 2 (
VECTOR
SPEED
VECTOR
:
): Identification magnetization is performed.
TORQ
2101
= 3 (
SCALAR FLYST
2101
has other value than 3 (
:
)], and/or
TORQ
) or 5 (
+
): Identification
FLY
BOOST
) or 5 (
SCALAR FLYST
FLY
Parameters