8.6
Information on insulation tests, protection class and degree of
protection
Insulation test
The insulation strength is demonstrated in the type test with the following test voltages in
accordance with IEC 61131-2:
Circuit
Rated voltage U
Ethernet connector
Degree of pollution and overvoltage category
The device meets the following requirements according to IEC 61131-2:2007:
Degree of pollution
Overvoltage category
Protection class
Protection class III according to IEC 61131-2
Protection against foreign objects and water
The device meets the requirements according to EN 60529.
Device side
Front
Rear panel
The front protection rating can only be guaranteed if the mounting seal lies flush against the
mounting cutout. Read the corresponding information in section
"Preparing the mounting cutout (Page 38)".
Comfort Panels
Operating Instructions, 07/2017, A5E36770603-AB

8.6 Information on insulation tests, protection class and degree of protection

Insulation tested with (type test)
24 V
707 V DC to other circuits / to ground
e
1500 V AC
2 (front)
1 (rear)
II
Degree of protection
When mounted:
IP65
Type 4X/Type 12 (indoor use only)
IP20
Protection against contact with standard test probes. There is no
protection against the ingress of water, dust and noxious gas.
Technical information
193