CHAPTER 4: SETPOINTS
RESET (Command)
SETPOINT
TYPE
Latched
Self-Reset
Pulsed
SETPOINT
OPERATE
Off = 0
Operation (from Protection,
Control, or Monitoring Elements)
SETTING
Relay ( Ready = 1)
BLOCK
Off = 0
Relay ( Ready = 1)
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
failsafe relay is de-energized in its normal non-activated state and will not change state
when control power is removed from the 869 (if not already activated by a protection
element).
The choice of failsafe or non-failsafe operation is usually determined by the motor's
application. In situations where the process is more critical than the motor, non-failsafe
operation is typically programmed. In situations where the motor is more critical than
the process, failsafe operation is programmed.
EVENTS
Range: Disabled, Enabled
Default: Enabled
Figure 4-31: Auxiliary Relays generic logic
This setpoint is displayed only
upon "Pulsed" output type selection
SETPOINT
SEAL-IN TIME
t
892828A3.cdr
OUTPUTS
Operate Aux Output Relay
FLEXLOGIC OPERAND
Aux Relay X ON
Relay (
Ready = 1)
4–105