1-6 FIELD SETTING / FUNCTION SETTING FOR OUTDOOR AIR UNIT

Function
Function
number
Filter
indicator
11
interval
Filter
13
indicator
action
Static pressure
26
*1 Auto
40
restart
Cool Air
43
Prevention
External
46
control
Error
report
47
target
Humidifier
63
l
contro
Setting number
Default
00
Standard
01
Longer
02
Shorter
00
Enable
01
Disable
Display only on
02
central remote
control
05
SP mode 05
06
SP mode 06
07
SP mode 07
08
SP mode 08
09
SP mode 09
10
SP mode 10
11
SP mode 11
12
SP mode 12
13
SP mode 13
14
SP mode 14
15
SP mode 15
16
SP mode 16
17
SP mode 17
18
SP mode 18
19
SP mode 19
20
SP mode 20
21
SP mode 21
22
SP mode 22
31
Normal SP
00
Enable
01
Disable
00
Prohibited
Follow the setting
01
on the remote
controller
00
Start/Stop
01
Emergency stop
02
Forced stop
00
All
Display only on
01
central remote
control
00
mode 00
01
mode 01
02
mode 02
Adjust the filter cleaning interval notification. If the notification is too
early, change to setting 01. If the notification is too late, change to
setting 02.
Enable or disable the filter
indicator. Setting 02 is for use
with a central remote control.
Range of static
Model name
SP mode 05 to 19
ARXH054GTAH
(50 to 185 Pa)
SP mode 05 to 20
ARXH072GTAH
(50 to 200 Pa)
SP mode 05 to 22
ARXH096GTAH
(50 to 220 Pa)
Enable or disable automatic system restart after a power outage.
Setting change prohibited.
Allow an external controller to start or stop the system, or to perform
an emergency stop, or to perform a forced stop.
* If an emergency stop is performed from an external controller, same
refrigerant system will be disabled.
* If forced stop is set,indoor unit stops by the input to the external input
terminals,and Start/Stop by a remote controller is restricted.
Change the target for reporting errors. Errors can either be reported in
all locations, or only on the wired remote.
Select control conditions of external output.
"Mode 00" is output when heating thermostat is ON, "Mode 01" is
output in heating operation, "Mode 02" is output in heating operation
and in fan operation.
01-21
Details
Normal static
pressure
pressure
185Pa
200Pa
200Pa