Mechanical Installation

4.2 Pre-installation

4.2.1 Planning the Installation Site

CAUTION
Before performing the installation it is important to plan
the installation of the frequency converter. Neglecting this
may result in extra work during and after installation.
Select the best possible operation site by considering the
following (see details on the following pages, and the
respective Design Guides):
Ambient operating temperature
Installation method
How to cool the unit
Position of the frequency converter
Cable routing
Ensure the power source supplies the correct
voltage and necessary current
Ensure that the motor current rating is within the
maximum current from the frequency converter
Ensure that the drive is properly protected per
local regulations.

4.2.2 Receiving the Frequency Converter

When receiving the frequency converter please make sure
that the packaging is intact, and be aware of any damage
that might have occurred to the unit during transport. In
case damage has occurred, contact immediately the
shipping company to claim the damage.

4.2.3 Transportation and Unpacking

Before unpacking the frequency converter it is
recommended that it is located as close as possible to the
final installation site.
Remove the box and handle the frequency converter on
the pallet, as long as possible.
AF-600 FP High Power Operating Instructions

4.2.4 Lifting

Always lift the drive in the dedicated lifting eyes. For all 4X
unit size and 52 unit size (IP00) Units, use a bar to avoid
bending the lifting holes of the drive.
Illustration 4.2 Recommended Lifting Method, 4X and 5X Unit
Sizes .
WARNING
The lifting bar must be able to handle the weight of the
drive. See Mechanical Dimensions for the weight of the
different Unit Sizes. Maximum diameter for bar is 2.5 cm (1
inch). The angle from the top of the drive to the lifting
cable should be 60°C or greater.
Illustration 4.3 Recommended Lifting Method, Unit Size 61
(460V, 600 to 900 HP, 575/600V, 900 to 1150 HP).
4
4
41