GE AF-600 FP Operating Instructions Manual page 115

Fan and pump drive 460v/575v 150hp and above
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

General Specifications
Analog inputs:
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R
Max. voltage
Current mode
Current level
Input resistance, R
Max. current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
7
7
Pulse inputs:
Programmable pulse inputs
Terminal number pulse
Max. frequency at terminal, 29, 33
Max. frequency at terminal, 29, 33
Min. frequency at terminal 29, 33
Voltage level
Maximum voltage on input
Input resistance, R
Pulse input accuracy (0.1 - 1 kHz)
Analog output:
Number of programmable analog outputs
Terminal number
Current range at analog output
Max. resistor load to common at analog output
Accuracy on analog output
Resolution on analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, serial communication:
Terminal number
Terminal number 61
The serial communication circuit is functionally seated from other central circuits and galvanically isolated from the supply
voltage (PELV).
114
AF-600 FP High Power Operating Instructions
i
i
i
53, 54
Voltage or current
Switch S201 and switch S202
Switch S201/switch S202 = OFF (U)
: 0 to + 10V (scaleable)
approx. 10 kΩ
± 20V
Switch S201/switch S202 = ON (I)
0/4 to 20mA (scaleable)
approx. 200 Ω
10 bit (+ sign)
Max. error 0.5% of full scale
200Hz
29, 33
110kHz (Push-pull driven)
5kHz (open collector)
see section on Digital input
28V DC
approx. 4kΩ
Max. error: 0.1% of full scale
0/4 - 20mA
500 Ω
Max. error: 0.8% of full scale
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Common for terminals 68 and 69
2
30mA
2
4Hz
1
42
8 bit