Dnp Implementation - GE 350 Communications Manual

Protective relay platform
Hide thumbs Also See for 350:
Table of Contents

Advertisement

DNP ETHERNET PROTOCOL SETTINGS

DNP implementation

OBJECT
OBJECT
VARIATION
NO.
NO.
1
0
1
2
2
0
1
2
3
10
0
2
12
1
20
0
1
2
5
3-14
DESCRIPTION
Binary Input (Variation 0 is
used to request default
variation)
Binary Input
Binary Input with Status
Binary Input Change
(Variation 0 is used to
request default variation)
Binary Input Change
without Time
Binary Input Change with
Time
Binary Input Change with
Relative Time
Binary Output Status
(Variation 0 is used to
request default variation)
Binary Output Status
Control Relay Output Block 3 (select)4
Binary Counter (Variation 0
is used to request default
variation)
32-Bit Binary Counter
16-Bit Binary Counter
32-Bit Binary Counter
without Flag
REQUEST
FUNCTION
QUALIFIER CODES
CODES (DEC)
(HEX)
1 (read) 22
00, 01 (start-stop) 06
(assign class)
(no range, or all) 07,
08 (limited quantity)
17, 28 (index)
1 (read) 22
00, 01 (start-stop) 06
(assign class)
(no range, or all) 07,
08 (limited quantity)
17, 28 (index)
1 (read) 22
00, 01 (start-stop) 06
(assign class)
(no range, or all) 07,
08 (limited quantity)
17, 28 (index)
1 (read)
06 (no range, or all)
07, 08 (limited
quantity)
1 (read)
06 (no range, or all)
07, 08 (limited
quantity)
1 (read)
06 (no range, or all)
07, 08 (limited
quantity)
1 (read)
06 (no range, or all)
07, 08 (limited
quantity)
1 (read)
00, 01(start-stop) 06
(no range, or all) 07,
08 (limited quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop) 06
(no range, or all) 07,
08 (limited quantity)
17, 28 (index)
00, 01 (start-stop)
(operate) 5 (direct
07, 08 (limited
op) 6 (dir. op,
quantity) 17, 28
noack)
(index)
1 (read) 7 (freeze)
00, 01 (start-stop) 06
8 (freeze noack) 9
(no range, or all) 07,
(freeze clear) 10
08 (limited quantity)
(frz. cl. noack) 22
17, 28 (index)
(assign class)
1 (read)7 (freeze)
00, 01 (start-stop) 06
8 (freeze noack) 9
(no range, or all) 07,
(freeze clear) 10
08 (limited quantity)
(frz. cl. noack) 22
17, 28 (index)
(assign class)
1 (read) 7 (freeze)
00, 01 (start-stop) 06
8 (freeze noack) 9
(no range, or all) 07,
(freeze clear) 10
08 (limited quantity)
(frz. cl. noack) 22
17, 28 (index)
(assign class)
1 (read) 7 (freeze)
00, 01 (start-stop) 06
8 (freeze noack) 9
(no range, or all) 07,
(freeze clear) 10
08 (limited quantity)
(frz. cl. noack) 22
17, 28 (index)
(assign class)
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 3: ETHERNET INTERFACE
RESPONSE
FUNCTION
QUALIFIER CODES
CODES (DEC)
(HEX)
---
---
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
---
---
129 (response)
17, 28 (index)
130 (unsol.
resp.)
129 (response)
17, 28 (index)
130 (unsol.
resp.)
---
---
---
---
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
129 (response)
echo of request
---
---
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

339345

Table of Contents