Task 4: Set up the network interface

Prerequisites
Procedure
92
The following information is required to set up the D400 network interface:
D400's assigned IP addresses (Maintenance and
Subnet Mask
Gateway address (if applicable)
This set up must be done the first time from the D400's front serial communications port.
To configure the network interface:
1.
Connect to the front maintenance port. See "Task 1: Connect to the D400" on page 90.
2.
At the D400#>> command prompt, enter d400cfg.
Result: The D400 Configuration Utility Menu appears.
Figure 52: D400 Configuration Utility Menu
3.
Enter 3. Configure Network Interface.
Result: The Available Network Interfaces menu appears.
In a multiple network interface configuration you are prompted to enter which device
to configure (NET1 or NET2).
4.
Enter 1. Net1, or enter 2. Net2.
Result: The Network Interface: Net1 or Net2 menu appears.
5.
Enter 2. Static IP Address.
Result: You are prompted to enter the D400 IP address.
6.
Enter the appropriate Static IP Addresses:
6.1.
Enter 1. Configure Maintenance IP Address.
Note: This entry is mandatory.
Result: You are prompted to enter the D400 IP Address.
GE INFORMATION
CHAPTER 6: SETTING UP THE D400
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL