Partner Stations - Siemens S7-1200 TELECONTROL Operating Instructions Manual

Hide thumbs Also See for S7-1200 TELECONTROL:
Table of Contents

Advertisement

Configuration and operation
4.9 STEP 7 configuration
Range
Nominal range (bipolar)
Underrange
(unipolar / life zero)
Underrange (bipolar)
Undershoot / wire break
Note
Evaluation of the value even when the option is disabled
If you enable one or both options and configure a value and then disable the option later, the
grayed out value is nevertheless evaluated.
To disable the two options, delete the previously configured values limit values from the input
boxes and then disable the relevant option.
Recommendation for quickly fluctuating analog values:
If the analog value fluctuates quickly, it may be useful to smooth the analog value first if limit
values are configured.
4.9.7.10

Partner stations

Options for specifying the communications partner
Telecontrol server enabled / Partners for inter-station communication
Here you specify who will be the communication partner of the data point.
If no CP was enabled as the partner for inter-station communication, the "Telecontrol server
enabled" option is selected automatically. In this case, the telecontrol server is the
communications partner of the data point.
If instead a CP of an S7 station should be the communications partner of the data point,
select the option "Partner for inter-station communication".
The telecontrol server and a CP in an S7 station cannot be selected as the partner at the
same time.
82
Raw value (16 bits) of the PLC tag
Decimal
Hexadecimal
27648
6C00
...
0
0000
...
....
-27648
9400
-1
FFFF
...
-4864
ED00
-27649
93FF
...
-32512
8100
-32768
8000
Module output [mA]
0 .. 20
(unipolar)
...
-0.001
...
...
-3.518
...
< -3.518
Operating Instructions, 10/2016, C79000-G8976-C311-02
-20 .. +20
4 .. 20
(bipolar)
(life zero)
20
...
0
...
-20
3.999
...
1.185
-20.001
...
-23.516
< 1.185
CP 1242-7 GPRS V2
Measuring
range [%]
100
...
0
...
-100
-0.004
...
-17.59
-100.004
...
-117.593
< -17.593

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-1200 - telecontrolCp 1242-7 gprs v2

Table of Contents