Character set for data point names
When you create a data point, a preset name "DataPoint_n" is adopted. In the data point
table and in the "General" tab of the data point you can change the name of the data point.
When assigning names only ASCII characters from the band 0x20 ... 0x7e may be used with
the exceptions listed below.
The following characters are forbidden since they do not adhere to the syntax rules of TCSB
for OPC items:
Non-permitted characters: . ' [ ] / \ |
period, apostrophe, square brackets, slash, back slash, vertical line (pipe)
4.9.7.2

Datapoint types

During the configuration of the user data to be transferred by the CP, each data point is
assigned a protocol-specific data point type. The data point types supported by the CP along
with the compatible S7 data types are listed below. They are grouped according to format
(memory requirements).
As of the firmware version named in the preface along with STEP 7Basic V14, the CP
supports the following data point types and data types.
Supported data point types of the CP
Table 4- 1
Format (memory re-
quirements)
Bit
Byte
Integer with sign (16 bits) Analog input
Counter (16 bits)
Integer with sign (32 bits) Analog input
Counter (32 bits)
Floating-point number
with sign (32 bits)
Floating-point number
with sign (64 bits)
Block of data
(1 .. 64 bytes)
For the possible formats of the ARRAY data type, refer to the following section.
1)
CP 1242-7 GPRS V2
Operating Instructions, 10/2016, C79000-G8976-C311-02
Supported data point types and compatible S7 data types
Data point type
Digital input
Digital output
Digital input
Digital output
Analog output
Counter input
Analog output
Counter input
Analog input
Analog output
Analog input
Analog output
Data
Data
Configuration and operation
4.9 STEP 7 configuration
S7 data types
Address area
Bool
I, Q, M, DB
Bool
Q, M, DB
Byte, USInt
I, Q, M, DB
Byte, USInt
Q, M, DB
Int
I, Q, M, DB
Int
Q, M, DB
Word, UInt
I, Q, M, DB
DInt
Q, M, DB
DInt
Q, M, DB
UDInt, DWord
I, Q, M, DB
Real
Q, M, DB
Real
Q, M, DB
LReal
Q, M, DB
LReal
Q, M, DB
ARRAY
DB
1)
ARRAY
DB
1)
67