Cooling fans
Supply, inverter and brake module cooling fans
The actual lifespan of the fan depends on the running time of the fan, ambient
temperature and dust concentration. Each supply and inverter module has its own
cooling fan. Replacements are available from ABB. Do not use other than ABB
specified spare parts.
The application program keeps track of the running time of the cooling fan of the
inverter modules. See the Firmware manual of the drive application program for the
actual signal which indicates the running time.
Replacing the fan of the supply module
WARNING! Read and follow the instructions in chapter
the instructions can cause physical injury or death, or damage to the equipment.
1. Switch off the power to the unit and open the main disconnecting device. Close
2. Let the intermediate circuit DC capacitors discharge for five minutes. Ensure by
3. Open the supply module cubicle doors.
4. Loosen the locking screw (marked with letter A in the figure below).
5. Disconnect the fan wiring plug (B).
6. Pull out the fan (C).
7. Install a new fan in reverse order.
the grounding switch (option +F259) if there is one.
measuring that the drive is not live before starting the work.
B
C
A
Safety
instructions. Ignoring
Maintenance
115