Specifications
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Pulse frequency range
(Duty cycle) Min. pulse width
Input resistance, R
Safe stop Terminal 37
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Maximum voltage on input
Typical input current at 24V
Typical input current at 20V
Input capacitance
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1)
Terminals 27 and 29 can also be programmed as output.
2) See 2.4.5.7 Terminal 37 for further information about terminal 37 and Safe Stop.
Analog inputs:
Number of analog inputs
Terminal number
0
10
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R
Max. voltage
Current mode
Current level
Input resistance, R
Max. current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
72
AF-650 GP Operating Instructions
2)
2)
i
2)
(Terminal 37 is fixed PNP logic):
i
i
4 (6)
1)
1)
18, 19, 27
, 29
, 32, 33,
PNP or NPN
0 - 24V DC
< 5V DC
> 10V DC
> 19V DC
< 14V DC
28V DC
0 - 110kHz
approx.4 kΩ
0 - 24V DC
< 4V DC
>20V DC
28V DC
50mA rms
60mA rms
400nF
53, 54
Voltage or current
Switch S201 and switch S202
Switch S201/switch S202 = OFF (U)
-10 to +10V (scaleable)
approx. 10 kΩ
± 20V
Switch S201/switch S202 = ON (I)
0/4 to 20 mA (scaleable)
approx. 200 Ω
30 mA
10 bit (+ sign)
Max. error 0.5% of full scale
100 Hz
1)
4.5ms
2