5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
•
Each terminal has specified functions it is capable
of performing
•
Parameters associated with the terminal enable
the function
•
For proper drive functioning, the control
terminals must be
Wired properly
Programmed for the intended function
Receiving a signal
See Table 2.2 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in K-03 Regional Settings.)
The following example shows accessing Terminal 18 to see
the default setting.
1.
Press [Main Menu] twice, scroll to Parameter Data
Set and press [OK].
2.
Scroll to parameter group E-## Digital In/Out and
press [OK].
AF-650 GP Operating Instructions
3.
4.
5.4 International/North American Default
Parameter Settings
Setting K-03 Regional Settings to [0]International or [1]
North America changes the default settings for some
parameters. Table 5.1 lists those parameters that are
effected.
Parameter
K-03 Regional
Settings
P-07 Motor Power
[kW]
P-02 Motor Power
[HP]
F-05 Motor Rated
Voltage
F-04 Base
Frequency
F-53 Maximum
Reference
F-54 Reference
Function
F-17 Motor Speed
High Limit [RPM]
See Note 3 and 5
F-15 Motor Speed
High Limit [Hz]
See Note 4
F-03 Max Output
Frequency 1
H-73 Warning
Speed High
E-03 Terminal 27
Digital Input
Scroll to parameter group E-0# Digital Inputs and
press [OK]
Scroll to E-01 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.
International
default parameter
value
International
See Note 1
See Note 2
230V/400V/575V
50Hz
50Hz
Sum
1500RPM
50Hz
132Hz
1500RPM
Coast inverse
5
North American
default parameter
value
North America
See Note 1
See Note 2
208V/460V/575V
60Hz
60Hz
External/Preset
1800RPM
60Hz
120Hz
1800RPM
External interlock
33
5