Catalog #
Rules
IC695ALG708
1.
The High Scale Value Engineering Units cannot be equal to the Low Scale Value Engineering
Units.
IC695ALG728
2.
The High Scale Value A/D Units must be greater than the Low Scale Value A/D Units.
3.
The High Alarm must be greater than the Low Alarm.
4.
The Alarm Limits must be within the configured Engineering Units minus User Offset range.
For example, if the High and Low Engineering Unit Scale values are 10,000 and -10,000 and
User Offset is 1000, the alarm limit range is +9,000 to -11,000.
5.
The valid range of Clamp Limits (if enabled) and Default Value is extended slightly beyond the
alarm limits minus User Offset, depending on the configured Range.
6.
Integer Current:
Floating Point Current:
Integer Voltage:
Floating Point Voltage:
7.
The minimum (slowest) ramp rate is the higher Engineering Unit Scale Value minus the lower
Engineering Unit Scale Value divided by 60,000. Put another way, the minimum ramp rate must
be no slower than the full Engineering Units range traversed in 60 seconds.
IC695ALG808
1. -7, Same as IC695ALG708
8.
Open Wire Enable Diagnostic reporting is only valid when the module's Range Type is
Voltage/Current and the Range is set to a Current Range.
9.
Short Circuit Enable Diagnostic reporting is only valid when the module's Range Type is
Voltage/Current and the Range is set to a Voltage Range.
1.
The counter High Range value must be greater than the Low Range Value.
IC695HSC308
2.
If a counter is configured as Continuous within high/low range or One-shot within high/low
range, the PreLoad Value must also be within the range.
3.
If 1ms is selected as the Timebase Units, the Timebase range is 1 to 429496.
If units are 1 µS, the range is 1 to 429496729.
If units are 100 nS, the range is 1 to 2147483647.
4.
To be used as a counter Setpoint Output an External Output must be configured as Setpoint(s)
on the Outputs Tab.
Basic Module Parameters
4.2.5.2
The module parameters define how the PNC scans and stores the module's data. The number of address
ranges varies by module and submodule. For discrete data, there is a starting address and a length for
input data and another starting address and length for output data. Analog data can be listed with each
analog value as a separate address and a length of one or as a group with the starting address listed and
an overall length value. What is available can depend on the Configuration Tool.
Input Data /
The address in the I/O Controller's reference memory for the module's data.
Output Data
For PACSystems CPUs: Discrete Data can be added to %G, %I, %Q, %T, and %M memory areas.
Non-Discrete Data can be added to %AI, %AQ, %R, %W, %G, %T, and %M memory areas.
Length
For discrete modules, the length of the input /output data is fixed and cannot be edited.
Other Data
Some modules have other data areas such as Module Status, ESCP Point Status, or Digital Filter
settings. Refer to PACSystems RX3i System Manual, GFK-2314, or the appropriate User's Manual for
more details about the data of each I/O Module.
GFK-2737F
±400 Eng Units (0-20mA +400 Eng Units only)
±0.4 Eng Units
±500 Eng Units
±0.5 Eng Units.
December 2016
Chapter 4. Configuration
(0-20mA +0.4 Eng Units only)
47