Resetting To Factory Settings - Siemens LOGO! CMR2040 Operating Instructions Manual

Simatic net logo! - industrial ethernet
Hide thumbs Also See for LOGO! CMR2040:
Table of Contents

Advertisement

Diagnostics and maintenance

6.5 Resetting to factory settings

6.5
Resetting to factory settings
Resetting to factory settings: Effect
Note
Data on the CMR will be deleted
With the functions for resetting to factory settings described here, all configuration data on
the CMR is deleted!
Note
CMR no longer reachable via VPN
When you reset to factory settings, the VPN configuration is deleted and the CMR is no
longer reachable via OpenVPN.
● Deleted data
The following data is deleted by resetting to factory settings:
– IP address of the LAN interface configured by the user
– All other configuration data in the memory of the CMR
– Configuration data on a plugged in SD card. The files "default.cfg" and "user.cfg" on
● Data not deleted
The following data is not deleted by resetting to factory settings:
– MAC address of the LAN interface:
Executing the "Reset to factory settings" function
Two methods are available for resetting to factory settings:
● Resetting using the WBM
For a description of the procedure, refer to the section Operating status (Page 80).
● Resetting using the "SET" button
For the number of times and duration of pressing the button, refer to the section The
"SET" button (Page 32).
For the LED reactions during resetting and restarting, refer to the section LEDs to display
operation (Page 30).
136
It is reset to the default factory set IP address 192.168.0.3.
the SD card will be deleted.
LOGO! CMR2020,
Operating Instructions, 10/2016, C79000-G8976-C356-03
LOGO! CMR2040