5. SYSTEM PARAMETERS
Parameter
Number
P0004
Parameter Filter
Filters the available parameters by functionality so that a more focussed commissioning
approach is possible. For example, with P0004=22, only the PI parameters will be visible.
Possible Settings:
0
"All parameters"
2
"Inverter"
3
"Motor"
7
"Commands & digital I/O"
8
"Analogue I/O"
10
"Setpoint channel & ramp generator"
12
"Drive features"
13
"Motor control"
20
"Communication"
21
"Alarms, warnings & monitoring"
22
"PI Controller"
Note:
It is possible to start the inverter with any setting of P0004.
Some parameters are "Commissioning only" parameters and can be viewed within this
"filter" parameter, but these can only be set using P0010=1 (Quick Commissioning). These
parameters are defined with the key symbol '
P0005
Display selection
Selects display for parameter r0000
Most common settings:
21
Actual frequency
25
Output voltage
26
DC link voltage
27
Output current
Note:
The settings here refer to read only parameter numbers. Please see the appropriate
"rXXXX" parameter descriptions for further details.
P0010
Parameter groups for commissioning
This setting allows the parameters to be filtered so that only those related to a group of
functions are selected, as shown in the table below.
Possible settings:
0
Ready to Run
1
Quick Commissioning
30
Factory setting
Notes:
1
This parameter must be reset to 0 before the inverter will run (Automatic when
P3900 ≠ 0 (default)).
2
The accessible parameters are also affected by the User Access Level parameter
(P0003).
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter Name
' in the right hand column.
International English
♦ ♦ ♦ ♦ P0003 User
Min
Access Level
Max
♦ ♦ ♦ ♦ P0004 Setting
[Default]
♦ ♦ ♦ ♦ Changeable
Units
♦ ♦ ♦ ♦ Status
0
1
22
All
[0]
'•'
-
0
2
4000
12
[0]
'•'
-
0
1
30
All
[0]
-
49