Chapter 7 Setting
When the output frequency is over the frequency that is set to C043 during deceleration, ZSW1
bit10 becomes ON. If you set C043 to 0, ZSW1 bit10 doesn't become ON.
7.2.13 C102 (Reset selection)
You need to set 03 (release at tripping) to C102. This parameter decides the WJ200 / WL200's
action when the reset terminal (RS) is ON.
If you set C102 to 00 (release at ON), 01 (release at OFF), or 02 (enable at tripping), WJ-PN is reset
at reset terminal (RS) input and WJ200 / WL200 displays E60 (option error). If you set 03 (clear
tripping state only), WJ-PN is not reset terminal (RS) input and WJ200 / WL200 can continue driving
after released from tripping.
7.2.14 P044 (Communication watchdog timer (for option))
You need to set P044 to the communication watchdog timer. This communication watchdog timer is
different from the watchdog of PROFINET. This communications watchdog timer starts the time
measuring after the watchdog of PROFINET occurs. In case that the watchdog of PROFINET occurs
and then WJ-PN restarts communicating with PROFINET IO controller within time have been set in
P044, WJ-PN doesn't detect communication error.
non communication.
7.2.15 P045 (Inverter action on communication error (for
option))
You need to set P045 to inverter action on communication error.
7.2.16 P160 - P169 (Option I/F command register to write 1 to
10)
You need to set P160 - P169 to Modbus register no when you use telegram 103, 104 or 105. Please
refer to "8.12.2 WJ-PN telegram 103 to 105" for details.
7.2.17 P170 - P179 (Option I/F command register to read 1 to
10)
You need to set P170 - P179 to Modbus register no when you use telegram 103, 104 or 105. Please
refer to "8.12.2 WJ-PN telegram 103 to 105" for details.
7.2.18 P200 (Register Mapping setting)
This parameter exists in WJ200 Ver.3.0 or later.
You need to set P200 to 00 when you use WJ-PN.
If you set P044 to 0, WJ-PB doesn't monitor