Mounting And Connections; Mounting The Q9 Flowsaver - Toshiba Q9 Installation And Operation Manual

Flowsaver/bypass low voltage variable torque hvac inverter
Table of Contents

Advertisement

Mounting and Connections

The Q9 F
one enclosure, and the two-part system; the ASD and the Bypass Box as two separate components.
The mounting and connection requirements vary when discussing the one-piece and the two-piece
systems. The two-piece system is identified as the BYP Series in this publication. The term
Q9 F
LOW
specifics of the BYP Series. The systemic functionality is identical for both system versions and no
differentiation is required. Mechanical enclosure differences are specified as required.
The Q9 F
connections and settings. To operate properly, the Q9 F
connected to a power source (3-phase AC input at the L1, L2, and L3 terminals). The control terminals
of the Q9 F
the proper sensors or signal input sources (see the section titled
for an expanded description of the system control options).
The output terminals of the system (T1, T2, and T3) must be connected to the motor that is to be
controlled. See
As a minimum, the installation of the ASD shall conform to Article 110 of the NEC, the Occupational
Safety and Health Administration requirements, and to any other local and regional industry codes
and standards.
Mounting the Q9 F
The ambient operating temperature rating for the Q9 F
The process of converting AC to DC, and then back to AC produces heat. During normal ASD
operation, up to 5% of the input energy to the ASD may be dissipated as heat.
Install the Q9 F
enclosure.
Mount the system in a location that is in a well ventilated area that is not in the path of direct sunlight.
When installing multiple ASDs, ensure that there is a clearance space of at least 8 inches (20 cm) from
the top and the bottom of adjacent units. Ensure that the ventilation openings are not obstructed. There
should be at least 5 cm (2 inches) on either side of adjacent units. For the models below 50 HP the top
and bottom clearance specifications may be reduced to 4 inches (10 cm). This space ensures that
adequate ventilation is provided (see the section titled
on pg. 35
Do Not operate the ASD with the enclosure door open.
ASDs produce high-frequency noise — steps must be taken during installation to avoid the negative
effects of noise. Listed below are some examples of measures that will help to combat noise problems.
Separate the input and output power conductors of the main circuit. Do not install the input and
output wires in the same duct or in parallel with each other, and do not bind them together.
Do not install the input or output power conductors of the main circuit and the wires of the control
circuit in the same duct or in parallel with each other, and do not bind them together.
Use shielded wires or twisted wires for the control circuits.
Ensure that the grounding terminals (G/E) of the ASD are securely connected to ground.
Connect a surge suppressor to every electromagnetic contactor and relay installed near the ASD.
Install noise filters as required.
Q9 FlowSaver Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
S
is available in two typeform-specific versions: the ASD and the Bypass system in
LOW
AVER
S
will be used throughout this publication to address both types unless addressing
AVER
S
may be set up initially by performing a few simple system configuration
LOW
AVER
S
may be used by connecting the terminals of the Terminal Board (P/N 53750) to
LOW
AVER
Figure 7 on pg. 29
for the connection diagram of the Q9 F
LOW
S
securely using the four mounting holes on the top and bottom of the
LOW
AVER
for additional information on mounting space requirements).
S
must be securely mounted and
LOW
AVER
I/O Monitoring and Control on pg. 24
S
AVER
S
is from 14° to 104° F (-10° to 40° C).
LOW
AVER
Enclosure Dimensional Information and Weights
S
.
LOW
AVER
19

Advertisement

Table of Contents
loading

Table of Contents