APPENDIX B
ADDRESS BIT
NAME
Ajustes Sobreintensidad Temporizada de Fases Nivel Alto Grupo 1 - Phase TOC High 1 Settings(cont.)
0x23AD
Voltage Restraint
0x23AE
Snapshot Events
0x23C1
Confirmation address
Ajustes Sobreintensidad Temporizada de Fases Nivel Alto Grupo 2 - Phase TOC High 2 Settings
0x23C2
Function
0x23C3
Input
0x23C4
Pickup Level
0x23C6
Curve
0x23C7
TD Multiplier
0x23C9
Reset
0x23CA
Voltage Restraint
0x23CB
Snapshot Events
0x23DE
Confirmation address
Ajustes Sobreintensidad Temporizada de Fases Nivel Alto Grupo 3 - Phase TOC High 3 Settings
0x23DF
Function
0x23E0
Input
0x23E1
Pickup Level
0x23E3
Curve
GEK-113285A
FORMAT STEP MODE LENGTH MISCELLANEOUS
F012
1
F012
1
F012
1
F012
1
F003
1
F012
1
F003
1
F012
1
F012
1
F012
1
F012
1
F012
1
F003
1
F012
1
G650 Generator Protection & Control System
1=LINEAR
R/W
1
0=DISABLED
1=ENABLED
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
1
0=PHASOR(DFT)
1=RMS
R/W
2
[0.05 , 160.00] A
R/W
1
0=IEEE Ext Inv
1=IEEE Very Inv
2=IEEE Mod Inv
3=IEC Curve A
4=IEC Curve B
5=IEC Curve C
6=IEC Long-Time Inv
7=IEC Short-Time Inv
8=IAC Ext Inv
9=IAC Very Inv
10=IAC Mod Inv
11=ANSI Ext Inv
12=ANSI Very Inv
13=ANSI Norm Inv
14=ANSI Mod Inv
15=I2t
16=Definite Time
17=Rectifier Curve
18=User Curve A
19=User Curve B
20=User Curve C
21=User Curve D
R/W
2
[0.00 , 900.00] s
R/W
1
0=INSTANTANEOUS
1=LINEAR
R/W
1
0=DISABLED
1=ENABLED
R/W
1
0=DISABLED
1=ENABLED
W
1
R/W
1
0=DISABLED
1=ENABLED
R/W
1
0=PHASOR(DFT)
1=RMS
R/W
2
[0.05 , 160.00] A
R/W
1
0=IEEE Ext Inv
1=IEEE Very Inv
2=IEEE Mod Inv
B.7 MEMORY MAP