Reyrolle protection relay
+ve
Provides continuous Trip circuit supervision of all wiring and links with Breaker Open or Closed.
Auxilliary
Status
Voltage
Voltage
110/125 V
48 V
110/125 V
110/125 V
220/250 V
220/250 V
Note 1:- Worst case current - Short circuit applied across Status input with CB Closed and max Auxilliary Voltage.
Resistors must be at least 18 Watt rated and connected using crimped connections as under worst case they will
run hot.
Figure 3.8-2
This scheme provides continuous, high security, Trip Circuit Supervision of all wiring and links with circuit breaker
Open or Closed. Note a TCS Alarm will be generated if the trip contact is latched.
3.9

Output Relays

The output relays in the Argus range can be programmed to be self or hand reset. In the hand reset mode, a
status input can be programmed to electrically reset the hand reset output relays. In Figure 3.2-1, if the
transformers at A and B are, for example, 132 / 33kV or 132 / 11kV and, on the 132kV side there are no local
circuit breakers but motor operated isolators, then the reverse characteristic elements can be programmed to
operate a hand reset output relay. This relay can be wired to give an intertrip signal and initiate isolator operation.
In due course, this output relay can be remotely reset by a status input.

3.10 Post-fault Analysis

Argus overcurrent protection relays provide extensive information for post-fault analysis; however, to use this
effectively the Argus must be correctly set when put into service. This section describes measures that should be
taken to ensure the correct data is captured in the event of a fault.

3.10.1 Events, Fault and Waveform Records

Fault records provide textual information on the source of the trip within the Argus, i.e. the element that tripped
and any elements that were picked up at the time of trip. This gives the first indication of the type of fault.
However, the fault record should be examined in coordination with the event records to see the full sequence of
events leading to a trip. It is possible to identify developing and flashing faults using the event records.
If a waveform record is available, the current waveforms (and voltage waveforms in some models) allow the type
of fault to be easily identified. However, the waveform record lasts only 1 second, whereas the event records will
cover many seconds or minutes. If a fault is of a flashing nature this will be apparent from the event records, while
the waveform record may show only the final overcurrent leading to trip.

3.10.2 Fault triggers

In order to generate a fault record it is important that the fault trigger is correctly set. A fault will be recorded if any
element trips and it is mapped to an output relay that is defined as a fault trigger relay. Therefore, any output relay
that trips a circuit breaker should be set as a fault trigger relay using the Data Storage:Fault Trigger setting. In
addition, if it is required to record a fault for any other element, an output relay driven by that element should also
be defined as a fault trigger relay.
©2013 Siemens Protection Devices Limited
Trip contacts
Trip Link
Rs
Status input
Rs
Rd
2K7
2K7
4K7
4K7
10K
10K
Engineering Recommendations S.15 H5 Trip Circuit Supervision scheme
Circuit breaker
Open position
Rd
Auxiliary contacts
I
I
TRIP COIL
TRIP COIL
CB Open
CB Closed
< 20 ma
< 35 ma
< 2.5 ma
< 5 ma
< 2.5 ma
< 5 ma
7SG11 Argus Technical Reference
Trip coil
Note1
I
TC max
CB Closed
< 55ma
< 35 ma
< 30 ma
P300005 Application Diagrams / TCS H5
P20007 Page 62 of 71