Table 13 Structure Of The Parameter Record Of A User - Siemens SIMATIC NET CP 243-1 IT Technical Manual

Communications processor for industrial ethernet and information technology
Table of Contents

Advertisement

Configuration
Parameter
Access rights
The access rights are represented in
hexadecimal format.
Bit [0-1] Not used
Bit [2] Read access to data of the S7-
200 CPU via the HTTP server
0: No
1: Yes
Bit [3] Read and write access to data of
the S7-200 CPU via the HTTP
server
0: No
1: Yes
Bit [4-5] Not used
Bit [6] Access to status page of the CP
243-1 IT via HTTP server
0: No
1: Yes
Bit [7-15] Not used
Bit [16] Access to all FTP functions
0: No
1: Yes
Bit [17-31] Not used
User name
The user name is presented in plain text
and consists of 1 to 32 characters.
Password
The password is encrypted and stored
with a character length of up to 64 char-
acters (actual password length is be-
tween 1 and 32 characters).
Table 13
80
Description
Structure of the parameter record of a user
Example
00|00010048|<User name>|<Password>
- Read and write access via HTTP
- Access to status page of the CP 243-1
IT via HTTP server
- Access to all FTP functions
00|00000040|Status_CP|<Password>
The user with the user name Status_CP
is authorized to read the status of the
CP 243-1 IT.
00|00010000|<User name>|W9vQ}G cfH
The user with the password
!state_Cp1 (encrypted: W9vQ}G cfH) is
authorized to execute all FTP functions.